Description
Features
- Financing options offer you solutions that meet your budget.
- Electronic fuel & ignition control optimizes fuel use for a more cost-efficient and lower emission back-up power solution.*
- *On average versus Generac Guardian Series standby generators.
- Long, best-in-class service intervals mean you spend less time on maintenance and more time enjoying the comfort that comes with owning a standby generator.
- Remote diagnostics monitor your generator’s performance and help detect issues before they become a problem, helping you save time & money on maintenance.
- Built-in Cellular Connectivity allows you to monitor performance and control your generator with Mobile Link whether you’re home or away.
- Mobile LinkTM keeps you connected and provides real-time updates and maintenance alerts.*
- *Requires Mobile Link TM premium subscription
- Oil level sensors monitor oil level to help ensure generator readiness.
- Improved cold start performance enables generator start-up in cold climates.
- Sloped roof and rear air intake reduce risk of snow and ice intrusion.
- Compatible with ecobee by Generac thermostats and Generac PWRcell battery systems to seamlessly monitor & control your home’s energy.
- Every Generac Standby Generator comes with a 5-year limited warranty, and over 65 years of innovation behind it.
- 24/7/365 Customer Support Team is ready all day, every day, from our headquarters in Wisconsin to answer any questions you might have.
- Generac generators and engines are engineered and assembled in the USA*.
What’s in The Box
- 28kW Generac Air Cooled Standby Generator
Warranty
- 5 Year Limited Warranty
- 30 Day Satisfaction Gauranteed
Specifications
| SKU | GNC-7282 |
| Model | 28 kW |
| Rated maximum continuous power capacity (LP) | 28 kW* |
| Rated maximum continuous power capacity (NG) | 25 kW* |
| Rated voltage | 240 V |
| Rated maximum continuous load current – 240 Volts (LP / NG) | 116 / 104 |
| Total Harmonic Distortion | Less than 5% |
| Main line circuit breaker | 125 amp |
| Phase | 1 |
| Number of rotor poles | 2 |
| Rated AC frequency | 60 Hz |
| Power factor | 1.0 |
| Battery requirement (not included) | 12 volts, AGM Powersport Battery Group BTX20L 310CCA minimum |
| Dimensions (L x W x H) in / cm | 46.4 x 26.3 x 30.7 / 117.9 x 66.8 x 77.9 |
| Sound output at 23 ft (normal load) | 67 dB(A) |
| Sound output at 23 ft (Quiet-Test mode) | 55 dB(A) |
| Engine type | GENERAC G-Force 1000 Series |
| Displacement | 997 cc |
| Fuel consumption Natural Gas 1/2 Load | 182 ft³/hr (5.15 m³/hr) |
| Fuel consumption Natural Gas Full Load | 297 ft³/hr (8.41 m³/hr) |
| Fuel consumption Liquid Propane 1/2 Load | 81 ft³/hr (2.23 gal/hr) [8.45 L/hr] |
| Fuel consumption Liquid Propane Full Load | 144 ft³/hr (3.97 gal/hr) [15.02 L/hr] |
| Controls AUTO | Automatic start on utility failure; programmable exerciser |
| Controls MANUAL | Start with starter control; unit stays on; transfers to load if utility fails |
| Controls OFF | Stops unit; generator will not automatically start on utility failure; control and charger operate if utility is available |
| Controls SERVICE | For diagnostic personnel use to prevent remote commands and nuisance Mobile Link notifications during testing |
| Ready to Run/Maintenance messages | Standard |
| Engine Run Hours indication | Standard |
| Programmable start delay | 2–1,500 seconds (dealer programmable) |
| Utility nominal voltage setting | Adjustable 90–110% of 240V (default 100%) |
| Utility Voltage Loss/Return to Utility (brownout setting) | Adjustable 75–80% dropout / 84–89% pickup |
| Future Set Capable Exerciser/Exercise Set Error warning | Standard |
| Run/Alarm/Maintenance logs | 50 events each |
| Engine start sequence | Cyclic cranking; engine cranks a maximum of five times at factory set intervals and durations |
| Starter lock-out | Starter cannot re-engage until 5 sec after engine has stopped |
| Smart battery charger | Standard |
| Charger Fault/Missing AC warning | Standard |
| Low Battery/Battery Problem Protection and Battery Condition indication | Standard |
| Automatic Voltage Regulation with Over and Under Voltage protection | Standard |
| Under-Frequency/Overload/Stepper Overcurrent protection | Standard |
| Safety Fused/Fuse Problem protection | Standard |
| Automatic Low Oil Pressure/High Oil Temperature shutdown | Standard |
| Overcrank/Overspeed (@ 72 Hz)/RPM Sense Loss shutdown | Standard |
| High Engine Temperature shutdown | Standard |
| Internal Fault/Incorrect Wiring protection | Standard |
| Common external fault capability | Standard |
| Automatically upgradable firmware via Cellular or Wi-Fi | Standard |